Brand Name : HRESYS
Model Number : VHR 12DT120
Certification : CE
Place of Origin : China
MOQ : 10 Pcs
Price : Negotiable
Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability : 1800000 PCS/YEAR
Delivery Time : 30 DAYS
Packaging Details : Box/carton(standard package)
Product Name : 12 V Lead-acid Batteries
Capacity : 120 Ah
Float Charge Voltage : 13.6V/block @25℃
Weight : 35.8kg (78.9 lbs.)
Application : Security and alarm system
Nominal Voltage (V) : 12 (6 cells per unit)
Internal Resistance : Approx. 0.004 Ohm (fully charged@20℃)
Dimension : L408mm x W177mm x H223mm
12V 120AH Duration Top Terminal Lead-acid Batteries for Security and alarm system, L408mm x W177mm x H223mm
· Excellent cyclic performance thanks to thick plate with excessive active material enables
· Silicon Gel technology applied in electrolyte to prevent water loss and to resist thermal runaway
· Available for multiple applications
· Wide operation temperature range
Nominal Voltage (V) | 12 |
Nominal Capacity (25 C) | 120 Ah@C10 (to 1.80Vpc) |
Dimension (mm) | L408mm x W177mm x H223mm |
Approx. Weight | 35.8 kg (78.9 lbs.) |
Terminal Type | Female Copper Insert M8 |
Internal Resistance | Approx. 0.004 Ohm (fully charged@ 20°C) |
Max. Charge Current | 30 A |
Self-Discharge | Approx. 3% per month @ 25°C |
Ambient Temperature | Discharge: -20~55°C Charge: -20~50 °C Storage: -20~45°C |
Float Charge Voltage | 13.6V/block @25℃ |
Equalize Charge Voltage | 14.4V/block @25℃ |
Container Material | ABS (UL94-V0 optional) |
HRESYS DT Series Duration Top Terminal Valve Regulated Lead Acid Battery is specially designed for UPS
Applications including telecom, UPS, IDC, security and alarm system, utilities, emergency light systems, CATV and other backup applications.
With corrosion resistance thick grid, international leading technologies and State-of-the-art automated manufacturing, DT series offer long cycle life, large current discharge capability, high consistency reliability and safety, and environmental-friendly.
o Outdoor telecom
o UPS
o IDC
o Security and alarm system
o Utilities
o Emergency light systems
o CATV
o IEC 6 - 1056-1
o GB/T 22199
o GB/T 19639-1
o JIS C870 - 2 1
o ISO9001:2015
o ISO14001:2015
o OHSAS18001:2007
o CE Certificate
· Cyclic Characteristics
High cycle performance: up to 550 cycle at 80%DOD
![]() |